Compact filters

Ecofil® fine dust filter FP

Ecofil® FP Fine Dust Filters remove air contamination such as fine dust, smoke, vapor, soot, pollen, bacteria, etc. and are therefore ideally suitable as final filters or as pre-filters for HEPA- or ULPA- filters in air conditioning installations.

Ecofil® FP filters are suitable for all standard filter applications, especially with those requiring increased Service Life, Safety and Versatility. Ecofil® FP Filters are available in 8 efficiencies, 4 nominal sizes, 2 depths and 2 models (NT/HT).

Application parameters

Continuous operating temperature

  • Model »NT«: <75 °C
  • Model »HT«: <120 °C (not valid for FP-65)

Pressure drop

  • recommended final pressure drop: 450 Pa
  • max. final pressure drop (endurance strength): 800 Pa
  • bursting pressure (new filter): >1500 Pa

Admissible relative humidity

  • FP-65: <85 %
  • FP-M6 to FP-F9: < 100 %

Materials

Filter media

  • FP-65: 18 m2 cellulose fibre paper
  • FP-M6 to FP-F9: 18 m2 glass fibre paper, zigzag folded to form mats

Frame »NT«

  • Incinerable halogen free recycled Polystyrol

Frame »HT«

  • Plastics and galvanized steel

Sealent

  • Polyurethane

Flammability classifications of materials used

  • Model »NT«: K2/F2 according to DIN 53438
  • Model »HT«: K1/F1 according to DIN 53438

The superior solution

  • Comprehensive range – independently tested.
  • Low pressure drop -maximum economy.
  • Large filter surface of 18 m2:

–          extremely long service life;

–          nominal air flow up to 5.000 m3/h.

  • Glassfibrepaper – no fibreloss.
  • Self-supporting rigid structure – high bursting pressures, dust migration impossible.
  • Direction of air flow and installation can be chosen either way round.
  • Without pollutant emission, fully incinerable – recyclable materials.
  • Frame manufactured from recycled plastics.
Technical data - Ecofil® fine dust filter FPFP-65-610M6-610F7-610F8-610F9-610
Air flow (normal service life)m³/h5.0005.0005.0005.0004,250
Initial pressure dropPa140135140150140
Nominal air volume (long service life)m³/h4.2504.2504.12504.2503.400
Initial pressure dropPa105100105120105
Filter class EN 779:2012/M6M6F7F8F9
Average atmospheric efficiencyEN 779:2012%7070829396
Average gravimetric arrestanceEN 779:2012%>95>98>99>99~100