Compact filters

Ecofil® fine dust filter FP
Ecofil® FP Fine Dust Filters remove air contamination such as fine dust, smoke, vapor, soot, pollen, bacteria, etc. and are therefore ideally suitable as final filters or as pre-filters for HEPA- or ULPA- filters in air conditioning installations.
Ecofil® FP filters are suitable for all standard filter applications, especially with those requiring increased Service Life, Safety and Versatility. Ecofil® FP Filters are available in 8 efficiencies, 4 nominal sizes, 2 depths and 2 models (NT/HT).
Application parameters
Continuous operating temperature
- Model »NT«: <75 °C
- Model »HT«: <120 °C (not valid for FP-65)
Pressure drop
- recommended final pressure drop: 450 Pa
- max. final pressure drop (endurance strength): 800 Pa
- bursting pressure (new filter): >1500 Pa
Admissible relative humidity
- FP-65: <85 %
- FP-M6 to FP-F9: < 100 %
Materials
Filter media
- FP-65: 18 m2 cellulose fibre paper
- FP-M6 to FP-F9: 18 m2 glass fibre paper, zigzag folded to form mats
Frame »NT«
- Incinerable halogen free recycled Polystyrol
Frame »HT«
- Plastics and galvanized steel
Sealent
- Polyurethane
Flammability classifications of materials used
- Model »NT«: K2/F2 according to DIN 53438
- Model »HT«: K1/F1 according to DIN 53438
The superior solution
- Comprehensive range – independently tested.
- Low pressure drop -maximum economy.
- Large filter surface of 18 m2:
– extremely long service life;
– nominal air flow up to 5.000 m3/h.
- Glassfibrepaper – no fibreloss.
- Self-supporting rigid structure – high bursting pressures, dust migration impossible.
- Direction of air flow and installation can be chosen either way round.
- Without pollutant emission, fully incinerable – recyclable materials.
- Frame manufactured from recycled plastics.
| Technical data - Ecofil® fine dust filter FP | FP- | 65-610 | M6-610 | F7-610 | F8-610 | F9-610 | |
| Air flow (normal service life) | m³/h | 5.000 | 5.000 | 5.000 | 5.000 | 4,250 | |
| Initial pressure drop | Pa | 140 | 135 | 140 | 150 | 140 | |
| Nominal air volume (long service life) | m³/h | 4.250 | 4.250 | 4.1250 | 4.250 | 3.400 | |
| Initial pressure drop | Pa | 105 | 100 | 105 | 120 | 105 | |
| Filter class | EN 779:2012 | / | M6 | M6 | F7 | F8 | F9 |
| Average atmospheric efficiency | EN 779:2012 | % | 70 | 70 | 82 | 93 | 96 |
| Average gravimetric arrestance | EN 779:2012 | % | >95 | >98 | >99 | >99 | ~100 |